The cargo compartment tests were to further evaluate SF6
and to study HFC 125 in this type of scenario. The main objective
of this evaluation program was to determine the decay characteristics
of these simulants while exposing them to different air leakage
rates and to compare the results with Halon 1301. SF6
was further evaluated by running two series of tests utilizing
a fire suppression metering system after the activation of the
main total-flooding system. In this scenario, the comparison
was based on the similarity of volumetric concentrations after
activating the metering system.
The evaluation
tests were conducted in the Fire Safety Section facilities at
the FAA William J. Hughes Technical Center; the test articles
used in this study were two different size aircraft, a narrow-body
aircraft and a wide-body aircraft. The narrow-body cargo compartment
had a total cargo volume of approximately 625 cubic feet while
the wide-body aircraft had a cargo volume of 2000 cubic feet.
Both compartments had a ventilation system to control the leakage
rate.
For economic reasons,
the narrow-body compartment was divided into two sections; the
section selected for this study had a volume of 300 cubic feet.
This small cargo bay was equipped with a leak system, a modular
total-flooding fire suppression system, an open-loop fire suppression
metering system, pressure valves, blowout panels, gas sampling
probes, and measuring instruments (Refer to figure 1). A variable-speed
fan and a perforated duct controlled the leakage rate of the
cargo compartment. The leak system was capable of providing a
maximum flow of 21 CFM. The leakage rate of the cargo bay was
set and measured using a digital anemometer (Omega Model HH-30).
The L-shaped perforated
duct had a height of 28", a width of 39", and a 3"
diameter orifice. This duct had a total of thirteen 1/2"
diameter holes. The holes on the horizontal leg were spaced 5"
apart from each other while the holes on the vertical leg of
the duct were spaced 2.5" apart. A Powerstat Variable Autotransformer
(PVA) controlled the fan rotational speed. It was planned that
three fan flow settings were going to be used during the testing
program: 2 CFM, 11 CFM, and 21 CFM. The leakage rate of 2 CFM
was obtained by opening two holes, one on each end of the duct
legs; the remaining holes remained closed. The PVA was set to
40%. The 11- and 21-CFM leakage rates were obtained by opening
all of the holes and removing the duct cap found at the top of
the vertical leg. The only difference between their settings
was how the PVA was dialed: 60% for the 11-CFM leakage rate and
100% for the 21-CFM leakage rate.
The small compartments
fire suppression system consisted of two modular systems: a total-flooding
system and a metering system. The total-flooding system consisted
of a Fenwal fire bottle connected to a 7/8" manifold with
a single nozzle at the end. The manifold was approximately 10' long. The fire bottle was activated using
an electronic control head. The open-loop metering system comprised
of a pressure-regulated cylinder, regulated to 40 psig, connected
to a 0.25" copper tube that had a single nozzle with a 0.35"
orifice at the other end; the metering system setting and size
were arbitrarily selected. This system was activated manually.
There were two types
of gas analyzers used in this test program: the Heat Technology
Laboratory (HTL) Halonyzer and the Rosemount 880A analyzer. The
Halonyzer, calibrated to detect the volumetric concentrations
of HFC 125 and Halon 1301, offered a gas collection capability
of 12 probes. This system was used in the small compartment and
with HFC 125 and Halon 1301 only due to its temporary availability.
Five Rosemount 880A analyzers, calibrated for HFC 125, Halon
1301, and SF6, were available for both compartments;
only one of the five analyzers was calibrated for SF6.
This equipment provided a gas collection capability of four probes
that could be used for Halon 1301 or HFC 125 and one probe for
SF6. Even though there were five analyzers on hand,
only one was used at a time during some of the testing in order
to maintain the same flow conditions and gas dynamics when testing
SF6. When the Halonyzer was used at the beginning
of this study, all 12 probes were used and where located in two
different trees. Each tree had six levels spaced 7.5" apart
vertically starting from the floor. The sampling probes, 0.25"
copper pipes and equal in length, were designed to convey samples
at a uniform flow rate from the sampling area to the analyzer
units.
During the wide-body
aircraft test series the entire 2000 ft3 compartment
was used. The ventilation system of this aircraft provided a
leakage rate of 50 CFM. This bay was equipped with four main
gas collection probes and eight backup probes. The fire suppression
system consisted of an unbalanced banked system with five nozzles.
A closed-loop fire suppression metering system was present but
was not used during these tests.

Discharge tests were conducted for all of the identified candidates
as well as the baseline agent using the following procedures.
The installed fire
bottle was charged with the desired agent to a weight that produced
a 5% volumetric concentration in the cargo compartment; there
is one exception to this initial concentration in the case of
HFC 125. During the first series of testing with HFC 125 in the
small compartment, the fire bottle was filled based on the equal
liquid fill approach rather than the equal volumetric concentration
approach; this resulted in an initial volumetric concentration
of 4.7%. This liquid fill approach maximizes agent density at
the point of discharge, provides a consistent energy source during
discharge, conserves the amount of gaseous nitrogen, and results
in equivalent nozzle discharge pressure (Grosshandler et al.,
1995). This approach was later changed during the large compartment
testing to produce an initial volumetric concentration of 5%.
The amount of Halon 1301 and SF6 used to achieve 5%
in the small compartment was 5.8 pounds and 5.7 pounds, respectively.
In the case of HFC 125, 4.4 pounds were transferred into the
fire bottle to achieve 4.7% volumetric concentration in this
compartment. The amount of agent for the large compartment testing
was 38.5 pounds of Halon 1301, 31.0 pounds of HFC 125, and 37.7
pounds of SF6. After charging the bottle with the
agent, the bottle was pressurized with nitrogen gas to 375 pounds
per square inch absolute.
After charging and
plumbing the bottle, the leak fan was set to the appropriate
leak rate. Once this was set, and the analyzer(s) was (were)
ready, the fire bottle was discharged simultaneously with the
activation of the data acquisition system. The data acquisition
then collected the compartment's concentration history, temperature,
ambient humidity, and leak rate. During the tests that were designed
to use the fire suppression metering system, the system was activated
when the volumetric concentration dropped below 3%. Tests without
the metering system ran for 30 minutes, and the tests with the
metering system ran for 45 minutes.
|