APPENDIX D-LAVATORY DISPOSAL
RECEPTACLE BUILT-IN EXTINGUISHER MINIMUM PERFORMANCE STANDARD
Lavatory Disposal Receptacle Built-In Extinguisher
Minimum Performance Standard
1. INTRODUCTION.
The U.S. Department of Transportation, Federal Aviation Regulations
(FAR), 14 CFR 121.308(b) requires that, "After April 29,
1987, no person may operate a passenger carrying transport category
airplane unless each lavatory in the airplane is equipped with
a built-in fire extinguisher for each disposal receptacle for
towels, paper, or waste located within the lavatory. The fire
extinguisher must be designed to discharge automatically into
each disposal receptacle upon occurrence of a fire in the receptacle."
The disposal receptacles are designed to comply with the requirements
contained in FAR 14 CFR 25.853 (f) which states, "Each receptacle
used for the disposal of flammable waste material must be fully
enclosed, constructed of at least fire resistance materials,
and must contain fires likely to occur in it under normal use.
The ability of the receptacle to contain those fires under all
probable conditions of wear, misalignment, and ventilation, expected
in service must be demonstrated by test." FAA Advisory Circular
25-17, "Transport Airplane Cabin Interiors Crashworthiness
Handbook" provides an acceptable method to show compliance
with this rule.
Currently, although not required by airworthiness regulations,
the typical aircraft lavatory disposal receptacle fire extinguisher
uses Halon 1301. For all practical purposes, the production of
halons ceased, as of 1 January 1994, under the provisions of
the Montreal Protocol, due to their identification as an ozone
destroying compound. As a result, a search for alternative agents
was conducted.
2. SCOPE.
To establish the minimum performance standards (MPS) that
an agent must meet and which provides an equivalent level of
safety to that of Halon, the performance of an agent is measured
against a standard test method. This document establishes the
fire load, trash disposal receptacle test article, test procedures,
and pass/fail criteria for built-in extinguishers for lavatory
disposal receptacles.
3. AGENT SELECTION GUIDANCE.
3.1 ENVIRONMENTAL.
The primary environmental characteristics to be considered
in assessing a new agent are Ozone Depletion Potential (ODP),
Global Warming Potential (GWP), and Atmospheric Lifetime. The
agent selected should have environmental characteristics in harmony
with international laws and agreements, as well as applicable
local laws. This MPS sets out the means of assessing the technical
performance of potential alternatives, but in selecting a new
agent it should be borne in mind that an agent which does not
have a zero or near zero ODP and the lowest practical GWP and
Atmospheric Lifetime may have problems of international availability
and commercial longevity.
3.2 TOXICOLOGY.
The toxicological acceptability of an agent is dependent on
its use pattern. As a general rule, the agent must not pose an
unacceptable health hazard for workers during installation and
maintenance of the extinguishing system. In areas where passengers
or workers are present or where leakage could cause the agent
to enter the passenger compartment, at no time should the agent
concentration present an unacceptable health hazard. Following
release during fire extinguishment, the cumulative toxicological
effect of the agent, its pyrolytic breakdown products, and the
by-products of combustion must not pose an unacceptable health
hazard.
4. REQUIREMENTS.
4.1 ENVIRONMENT.
The replacement agent must be approved under the Environmental
Protection Agency (EPA) Clean Air Act, Significant New Alternatives
Policy (SNAP) program, or other international governmental approving
program. Approved agents on the SNAP or other international list
must not exceed the established criteria for Ozone Depletion
Potential (ODP) and toxicity.
4.2 TOXICOLOGY.
The quantity of agent, when discharged into the protected
trash receptacle volume, shall not exceed the NOAEL in the occupiable
space within the lavatory. (See appendix A.)
4.3 FIRE PROTECTION.
The fire extinguisher must successfully extinguish a test
fire contained in the test receptacle after automatically discharging
into the trash receptacle test article.
Additional testing may be required to substantiate agent/system
effectiveness in trash receptacles larger than the 1.333 cu ft
volume test article. If an extinguishing system is to be used
on receptacles with internal volume larger than 1.333 cu ft,
it is the responsibility of the manufacturer to demonstrate the
effectiveness of a particular agent amount.
4.4 FIRE THREAT.
The fire threat that must be extinguished is a trash receptacle
test article (ref. Section 5.2) filled with crumpled paper towels.
The specific requirements for the fire load are contained in
Section 5.3
4.5 ACCEPTANCE CRITERIA.
Each lavatory trash receptacle automatic discharge extinguisher
must meet the following criteria:
- Five separate extinguisher tests must be performed and each
must extinguish the test fire.
- Extinguisher discharge performance must meet the following:
- The nozzle must activate when the temperature in the test
receptacle reaches 175oF + 5oF,
as measured in Section 5.2.3.2.
- The extinguisher must activate within 60 seconds of reaching
the above activation temperature.
- The discharge duration must not exceed 15 seconds.
- The test fire must be extinguished and must not re-ignite
or flare-up after the access panel to the test receptacle has
been opened.
- An extinguisher that meets the requirements for use in trash
receptacles up to 1.333 cu ft is acceptable for use in a smaller
receptacle, with a similar installation, without additional testing.
5.0 TEST REQUIREMENTS.
5.1 TEST CONDITIONS.
Each test must be performed under the following conditions:
- The ambient temperature must be 80oF +
20oF.
- The fire load materials described in Section 5.3 must be
conditioned to 70oF + 5oF and a
maximum of 55% relative humidity until moisture equilibrium is
reached for 24 hours. The test must be initiated within 30 minutes
of removal of fire load materials from the conditioning chamber
if the atmospheric conditions within the test area are different.
- Agent Temperature. Extinguishing systems which utilize
a remote agent bottle typically mounted external to the trash
receptacle with a protruding discharge tube must maintain an
agent temperature of 30oF or less at the time the
agent is discharged (i.e., time of eutectic release). Extinguishing
systems which are typically mounted internal to the trash receptacle
must maintain a 30oF agent temperature at the start
of the test (i.e., ignition of the fire load).
Examples of maintaining proper agent discharge temperature:
- Example 1. The agent may be kept in a separate cold
chamber during the test, ensuring that the temperature will be
at or below 30oF. The cold chamber should
be as close to the discharge point of the test article as possible,
to allow for the shortest possible transfer plumbing.
- Example 2. Overcooling of the agent may be used when
an accurate estimate of the elapsed time can be determined for
the eutectic device to open (i.e., the temperature at the top
of the test article will reach 175oF) after initiation of
the ignitor. This would allow the tester to back calculate the
maximum amount of time available to ensure that the agent is
at or below 30oF, once it is removed from
the cold chamber.
5.2 TEST APPARATUS.
The test standard trash receptacle and extinguisher bottle
installation is described below:
5.2.1 Trash Receptacle test Article.
The test receptacle must be constructed of either aluminum
or steel of 0.125 inch thickness (nominal). The test receptacle
for trash containers up to 1.333 cubic feet (.038 m3)
volume is shown in Figure D-1. All receptacle dimensions
are internal measurements.
The front of the test receptacle must contain a clear access
panel constructed of fire resistant polycarbonate or glass for
visual observation. The access panel must be 9.5 + 0.5
inch (24.13 cm) wide by 8.5 + 0.5 inch (21.59 cm) high
with the lower edge of the panel positioned 6 + 0.5 inch
(15.24 cm) from the bottom surface.
A 2-inch (5.08 cm)-diameter hole must be centered 2 inches
up the side of the test receptacle for igniter insertion and
must be sealed after insertion of the igniter.
The front and back face of the test receptacle must have six
1-inch (2.54 cm)-diameter holes (12 holes total) equally spaced
for ventilation which are equipped with a mechanism for quick
opening or closing.
A waste flap opening must be provided at the top of the test
receptacle. The opening must be 6.2 inches (15.75 cm) by 6.2
(15.75 cm). A plate which is no more than 0.5 inch (1.27 cm)
larger than the opening must be mounted 0.5 inch (1.27 cm) above
the opening.
The agent discharge tube (used on systems that are externally
mounted) must be centered in the top of the test receptacle,
pointing straight down and must protrude into the cabinet 1 inch
from the upper surface. A hole in the cabinet shall be provided
to allow insertion of the discharge tube, which must fit snugly
in the hole. Heat resistant tape can be used on the outer surface
of the cabinet to facilitate an airtight seal.
5.2.2 Ignition Source.
A standard electrical resistance igniter must be used. The
igniter shall consist of a nichrome wire (nominal 0.025 inch
diameter) with 15 loops of 0.25 inch diameter. The length of
the ignitor (loop section) must be 1.25 + 0.125 inch.
To ensure consistent test commencement, the voltage through the
igniter shall be adjusted to provide 1650 +50oF
at the center point. The temperature at the center point should
be calibrated as follows:
- Mount a thermocouple, as described in Section 5.2.3, in the
center of a vertically positioned ignitor device, making certain
that the wires do not come in contact with the igniter, as shown
in Figure
D-2. Ensure that the thermocouple reading device is functioning
properly and protect from drafts.
- Energize igniter and simultaneously start the timing device.
Measure temperature at 30, 60, and 90 seconds.
- Repeat 4 times for a total of 5 tests, using a new igniter
each time.
5.2.3 Thermocouples.
Three thermocouples are to be used for testing and must be
type K grounded with a nominal 30 American Wire Gauge (AWG) size
conductor.
- One thermocouple must be installed on the fire extinguisher
to measure surface temperature. To obtain the most accurate reading
of the agent temperature, it is recommended that the thermocouple
be placed over a non-painted area on the agent vessel and covered
using adhesive tape. Lightly sand the painted exterior of the
agent vessel if necessary.
- One thermocouple must be installed at the centerline of the
test receptacle, as defined in Figure D-1.
- One thermocouple must be placed to measure ambient temperature.
5.2.4 Instrumentation.
A data acquisition system or other suitable instrument
with an appropriate range must be used to measure and record
the output of the thermocouples.
5.2.5 Timing Device.
A stopwatch or other device must be used to measure the time
of ignition energizing, smoke generation, open flaming, agent
discharge, and extinguishment.
5.3 TEST FIRE LOAD.
The fire load shall consist of crumpled two-ply paper hand
towels having a total weight of 815 + 5g.
5.3.1 Paper Towel Specification.
Type: Bleached, C-Fold Deep Embossed handifold towels
External dimensions: 10.25 by 13.25 inches
Weight: 4.5 + 0.1 g per towel
Tensile Strength Dry (grams/inch): 707
Tensile Strength Dry (Kg/15mm): 0.42
Tensile Strength Wet (grams/inch): 189
Tensile Strength Wet (Kg/15mm): 0.11
Absorbency (sec/0.1 ml): 30
Note: all Tensile strength test results derived from average
of both directions
Towels manufactured by:
Fort
Howard Corporation
1919 South Broadway (54304)
P.O. Box 19130
Green Bay, WI 54307 |
Telephone: 1-800-558-7325
Fax: 1-800-635-6906
part number 244-00
|
Towels distributed
by:
W.W. Grainger Inc.
(713) 748-8280
part number 2U215
5.3.2 Paper Crumpling Specification.
Prior to loading the paper towels into the test receptacle,
they must be opened and crumpled to simulate used hand towels.
This can be accomplished by performing a free fill density procedure
in which 340 + 10 paper towels are crumpled to fill an
18- x 18- x 18-inch container to the top level to ensure similarity
of crumpling between the various testing facilities. This procedure
may require several attempts in order to achieve the proper crumpling
tightness.
5.4 TEST BOOTH OR CHAMBER.
The trash receptacle test article should be located in a booth
or room containing adequate ventilation capabilities. The maximum
air velocity directly adjacent to the test receptacle should
not exceed 50 feet per minute.
5.5 TEST PROCEDURE.
- Condition the fire load.
- Weigh the extinguisher and record the value.
- Set up data acquisition system.
- In the test receptacle, install and clamp the igniter 1 inch
above the ventilation holes at the approximate centerline of
the receptacle, as shown in Figure D-1. A clipping device or other
nonintrusive means may be used to prevent the ignition source
from skewing left or right when the paper is being loaded into
the receptacle.
- Installation of fire load. Remove the observation window
and begin loading the crumpled hand towels. Ensure that the entire
bottom of the test receptacle is fully covered with a layer of
precrumpled towels (also pack one or two precrumpled hand towels
under the ignitor to prevent damage during subsequent loading).
When approximately one-half of the paper is loaded, reinstall
the observation window and finish loading the remainder of 815
+ 5 g of crumpled towels into the receptacle through the
bin flap. If there is difficulty in fitting the entire 815g of
crumpled towels into the test receptacle, it can be shaken lightly
to provide adequate space. When all materials are loaded, the
edges of the observation window can be sealed with duct tape
to prevent air infiltration or agent release. The test must be
initiated within 30 minutes of removal of the fire load materials
from the conditioning chamber if the atmospheric conditions within
the test area or booth are different.
- Mount the conditioned fire extinguisher to the test receptacle
per the manufacturer's installation drawing, ensuring that the
agent temperature will be at or below 30oF at the
time of discharge (externally mounted type) as described in section
5.1.
- Record initial ambient, extinguisher surface, and test receptacle
temperatures.
- Start the data acquisition system.
- Energize the igniter (time =0) and begin to record the times
to relevant events as described below.
- Upon extinguisher discharge, remove power from the igniter,
immediately close all ventilation holes in the test receptacle,
and record the time of discharge. (It is critical that the ventilation
holes be closed immediately upon agent discharge to prevent the
agent from escaping). If the extinguisher does not discharge
within 5 minutes of the igniter energizing, the test should be
aborted and considered a non-test.
- If after 5 minutes from the conclusion of the agent discharge,
the temperature and visual observations indicate that combustion
has ceased, open and secure the access panel.
- If after a further 2 minutes reignition does not occur, empty
the compartment and spread the waste into a single layer, observe
and note any residual smoldering. Record the extent of fire load
consumption, presence or lack of smoldering, etc. If residual
smoldering is present, the test is a failure.
- If re-ignition occurs, the test is a failure. Extinguish
the fire using water or other environmentally friendly method.
- Weigh the discharged extinguisher to determine and record
weight of agent discharged.
5.6 TEST REPORT.
The test report must include the following:
- A complete description of the test receptacle and the fire
extinguisher, including photographs, if appropriate.
- Details of the test results should include the temperature
of the extinguisher surface, temperature of the receptacle, and
the times from ignition energizing to generation of smoke, open
flaming, agent discharge, and end of test.
For
further information contact Tim Marker at Tim_Marker@admin.tc.faa.gov
LAST UPDATED
7/26/99
|