MINIMUM PERFORMANCE
STANDARDS FOR AIRCRAFT CARGO COMPARTMENT BUILT-IN FIRE SUPPRESSION
SYSTEMS.
FAA Draft
January 1999
1. INTRODUCTION.
Federal Aviation Regulations (FAR's) and Joint Aviation Regulations
(JAR's) require fire suppression systems for some classifications
of cargo compartments. In the past, the aircraft industry has
selected Halon 1301 total flood fire suppression systems as the
most effective systems for complying with the regulations. Because
of the ban on production of Halon 1301, mandated by the Montreal
Protocol and effective January 1994, new fire suppression systems
will need to be certified when the use of Halon 1301 is no longer
viable. The tests described in this standard are one part of
the total FAA/JAA certification process for cargo compartment
fire suppression systems. Compliance with other applicable regulations,
some of which are listed below, is also required. Applicants
attempting to certify replacement systems are encouraged to discuss
the required process with regulatory agencies prior to conducting
testing.
1.1 APPLICABLE REGULATIONS.
The following existing FAR's/JAR's pertain to cargo compartment
fire suppression/extinguishing systems:
25.851. "(b) Built-in fire extinguishers. If a built
in fire extinguisher is provided
- Each built-in fire extinguishing system must be installed
so that
(i) No extinguishing agent likely to enter personnel compartments
will be hazardous to the occupants; and
(ii) No discharge of the extinguisher can cause structural
damage.
- The capacity of each required built-in extinguishing system
must be adequate for any fire likely to occur in the compartment
where used, considering the volume of the compartment and the
ventilation rate."
25.855. "(h) Flight tests must be conducted to show compliance
with the provisions of Sec. 25.857 concerning
- Compartment accessibility,
- The entries of hazardous quantities of smoke or extinguishing
agent into compartments occupied by the crew or passengers, and
- The dissipation of the extinguishing agent in Class C compartments.
(i) During the above tests, it must be shown that no inadvertent
operation of smoke or fire detectors in any compartment would
occur as a result of fire contained in any other compartment,
either during or after extinguishment, unless the extinguishing
system floods each such compartment simultaneously."
25.857. "(c) Class C. A Class C cargo compartment is
one not meeting the requirements for either a Class A or Class
B compartment but in which
- There is a separate approved smoke detector or fire detector
system to give warning at the pilot or flight engineer station.
- There is an approved built-in fire extinguishing system controllable
from the pilot or flight engineer stations;
- There are means to exclude hazardous quantities of smoke,
flames, or extinguishing agent, from any compartment occupied
by the crew or passengers;
- There are means to control ventilation and drafts within
the compartment so that the extinguishing agent used can control
any fire that may start within the compartment."
In addition to these regulations, the FAA issued Airworthiness
Directive 93-07-15 which required, among other things, that after
November 2, 1996 the Class B cargo compartments on Boeing Models
707, 727, 737, 747, and 757 and McDonnell Douglas Models DC-8,
DC-9, and DC-10 Series airplanes have improved fire protection
features. One of three options available to comply with this
AD is to modify Class B cargo compartments on these airplanes
to comply with the requirements for Class C compartments. This
option would require the installation of a fire suppression system.
One other area of rulemaking activity relating to cargo compartment
suppression system requirements is the "Revised Standards
for Cargo or Baggage Compartments in Transport Category Airplanes,
Final Rule", effective March 19, 1998. This rule eliminates
Class D cargo compartments on newly certified aircraft under
Part 25 and requires existing Class D compartments on Part 121
certified passenger aircraft to comply with the detection and
suppression/extinguishing system aspects of Class C cargo compartment
requirements by March 19, 2001. This rule was issued by the FAA
and at this time applies only to aircraft operated by U.S. based
airlines.
2. SCOPE.
This document establishes the minimum performance standards
(MPS) that a cargo compartment fire suppression system must meet.
It describes the tests that should be performed to demonstrate
that the performance of the replacement agent/systems equals
the performance of the currently approved Halon 1301 systems.
3. AGENT SELECTION GUIDANCE.
3.1 ENVIRONMENTAL.
The replacement agent must be approved under the Environmental
Protection Agency (EPA), Clean Air Act, Significant New Alternatives
Policy (SNAP) program, or other international governmental approving
program. The primary environmental characteristics to be considered
in assessing a new agent are Ozone Depletion Potential (ODP),
Global Warming Potential (GWP) and Atmospheric Lifetime. The
agent selected should have environmental characteristics in harmony
with international laws and agreements, as well as applicable
local laws. This MPS sets out the means of assessing the technical
performance of potential alternatives. In selecting a new agent
it should be noted that an agent which does not have a zero or
near zero ODP and the lowest practical GWP and Atmospheric Lifetime
may have problems of international availability and commercial
longevity.
3.2 TOXICOLOGY.
The toxicological acceptability of an agent is dependent on
its use pattern. As a general rule, the agent must not pose an
unacceptable health hazard for workers during installation and
maintenance of the suppression system. At no time should the
concentration present an unacceptable health hazard in areas
where passengers or workers are present or where leakage could
cause an agent to enter an occupied area. Following the release
of the agent during fire suppression, the cumulative effect of
the agent, its pyrolytic breakdown products, and the byproducts
of combustion must not pose an unacceptable health hazard.
FAR Parts 25.851, 25.855 and 25.857 all address the issue
of hazardous quantities of smoke, gas or extinguishing agent
in occupied compartments. Conducting the fire tests described
in this MPS does not address those issues. The FAA Technical
Center has conducted tests in an aircraft fuselage with inflight
airflow conditions. Data on the level of smoke, gases and extinguishing
agent in the normally occupied sections of the fuselage are available
for some suppression agents and systems.
4. TEST REQUIREMENTS.
4.1 TEST ARTICLE.
The fire tests are to be conducted inside a simulated below
floor cargo compartment of a wide body aircraft. The volume of
the compartment should be 2000 +/- 100 cubic feet. See figure
1. The leakage rate from the compartment should be 50 +/-
5 cubic feet per minute. The leakage from the compartment should
be configured to simulate the "U" shape of the cargo
door seals that would exist on an actual aircraft. This can be
done by installing perforated ducts inside the compartment in
the shape of the perimeter of a cargo door and then venting those
ducts outside the test article. A variable speed fan installed
in the exit of the duct should be used to draw air out of the
compartment. One inch diameter holes spaced at one hole every
5 inches in a round, four inch diameter steel duct has been shown
to be effective. The perforated ducts should be installed on
the opposite side of the cargo compartment from where the ignited
box for the bulk load and containerized load fire scenarios are
located. The make up air back into the compartment should be
evenly distributed and not from any one location.
4.2 INSTRUMENTATION.
Temperature measurements should be taken throughout the cargo
compartment. Type K chromel/alumel 22 gauge thermocouples have
been found to be effective at measuring temperatures in the range
these fire scenarios produce. Ceiling thermocouples should be
evenly spaced along the compartment ceiling with a maximum of
five feet between adjacent thermocouples. One of the ceiling
thermocouples should be installed directly above the initial
ignition location for all fire scenarios. The beads of the ceiling
thermocouples shall be 1 inch below the compartment ceiling.
At least one thermocouple should be placed on the compartment
sidewall one foot below ceiling level and centered on the fire
ignition location. The sidewall thermocouple should be installed
on the side of the compartment nearest the ignition location.
At least two additional thermocouples should be placed in and
above the box containing the igniter for the bulk and containerized
fire scenarios. The purpose of these two thermocouples is to
monitor and verify the ignition of the boxes. The readings are
not part of the acceptance criteria. Care should be taken to
prevent these thermocouples from contacting the energized coil
of nichrome wire.
A continuous gas analyzer with a real time display of the
gas concentration is required for the aerosol can scenario when
the suppression system is a gaseous total flood system. A continuous
gas analyzer may be required, depending on the suppression system
design, for the bulk load and containerized load scenarios. Section
4.4 describes the conditions when this may occur. The accuracy
of the analyzer shall be +/- 5% of the reading. The gas analyzer
is used to measure the concentration of the gaseous suppression
agent. The data sampling rate for all the temperature measurements
and the gas concentrations should be at least one data point
every 5 seconds.
A pressure transducer is also required for the aerosol can
fire scenario. The response time of the transducer should be
.02 seconds or faster. Omegaâ
manufactures several transducers suitable for this application.
The transducer should be mounted on the ceiling in the geometric
center of the compartment. The data sampling rate for the pressure
transducer should be at least 50 data points per second.
4.3 FIRE SCENARIOS.
The aircraft cargo compartment fire suppression system must
successfully control the following four different fire scenarios.
4.3.1 BULK FIRE LOAD.
The fire load for this scenario shall be single-wall corrugated
cardboard boxes, with nominal dimensions of 18" X 18"
X 18". The weight of the cardboard should be 0.11 lbs/ft2.
The boxes should be filled with 2.5 pounds of shredded newspaper,
loosely packed without compacting. The weight of the filled box
should be 4.5 +/- 0.4 lbs. The flaps of the boxes should be tucked
under each other with no staples or tape used. The boxes should
be stacked in two layers into the cargo compartment in a quantity
representing 30% of the cargo compartment empty volume. For a
2000 cubic foot compartment, this would require 178 boxes. The
boxes shall be touching each other without any significant air
gaps between boxes. The test fire is ignited by applying 115
VAC to a seven foot length of nichrome wire. The wire is wrapped
around several folded paper towels. The resistance of the nichrome
igniter coil should be approximately 7 Ohms. The igniter should
be placed into the center of a box on the bottom outside row
of the stacked boxes. Several ventilation holes should be placed
in the side of the box to ensure that the fire does not self
extinguish. Ten, 1.0" (2.54 cm) diameter holes
have been shown to be effective. See figure
2 and figure 3.
4.3.2 CONTAINERIZED FIRE LOAD.
The same type of cardboard boxes filled with shredded newspaper
and the same igniter used in the bulk load fire scenario should
be used in this scenario. The boxes should be stacked inside
an LD-3 container as shown in figure 4.The
boxes shall be touching each other with no significant air gaps
between them. The container shall be constructed of an aluminum
top and inboard side, a Lexan (polycarbonate) front and the remainder
of steel. Two rectangular slots for ventilation should be cut
into the container in the center of the Lexan front and in the
center of the sloping sidewall. The slots should be 12"
by 3" +/-1/4". See figure 5.The
igniter is placed in a box on the bottom row, in the corner nearest
the sloping side of the container and the Lexan. Ventilation
holes should be placed in the sides of the box. Ten, 1.0"
(2.54 cm) diameter holes have been shown to be
effective. Two additional, empty LD-3 containers are placed adjacent
to the first container. See figure 6.
4.3.3 SURFACE BURNING FIRE.
0.5 U.S. gallons (1.89 liters) of Jet A fuel in a square pan
should be used for this scenario. The pan should be constructed
of 1/8"steel and measure 2 feet by 2 feet by 4 inches high.
Approximately 13 fluid ounces (385 ml.) of gasoline or alcohol
should be added to the pan to make ignition easier. 2.5 gallons
(9.5 liters) of water placed in the pan has been found to be
useful in keeping the pan cooler and minimizing warping. This
quantity of fuel and pan size is sufficient to burn vigorously
for approximately 4 minutes if not suppressed. The position of
the pan in the cargo compartment should be in the most difficult
location for the particular suppression system being tested (higher
in the compartment for a heavier than air agent, lower for a
lighter than air agent, not directly under a discharge nozzle,
etc.)See figure 7.
4.3.4 EXPLODING AEROSOL CAN FIRE.
This scenario addresses the overpressure and bursting of an
aerosol can involved in a cargo fire and the potential for the
ignition of the released hydrocarbon propellant used in these
cans. The FAA Technical Center has developed an aerosol can simulator
that releases a mixture of propane and alcohol through a large
area valve and across sparking electrodes.
The aerosol explosion simulator must utilize a cylindrical
pressure vessel for the storage of flammable base product and
propellant. The pressure vessel must be capable of withstanding
a minimum pressure of 300 psi. The pressure vessel must be mated
to a ball-valve capable of withstanding a minimum pressure of
300 psi. The port diameter of the ball must be 1.5 inches (Note:
a ball valve is typically classified according to the diameter
of the pipe that it connects to, but this is not necessarily
the size of the ball port). The ball valve must be capable of
rotating from the fully closed position to the fully open position
in less than 0.1 seconds to allow the formation of a vapor cloud.
Longer opening durations will significantly affect the vapor
cloud formation, and hence the explosive force yielded. The ball
valve can be activated by any suitable means, including pneumatic
or hydraulic actuators, or manually via the appropriate linkage.
The pressure vessel must be mounted vertically above the ball
valve to allow for complete expulsion of the liquid contents.
A discharge elbow located vertically under the ball valve will
direct the contents horizontally. (figure
8,figure 9,figure
10).
Pressure Vessel. A steel 2-inch diameter, 9 inch long schedule
80 pipe welded or capped at one end has been found suitable for
storage of the pressurized mix.
Ball Valve. The 2-inch valve must be constructed of a material
capable of withstanding interaction with ethanol and propane.
A DynaQuipâ stainless steel
valve has been found suitable for this application.
Ball-valve actuator. A pneumatic rotary actuator has been
found suitable for quickly and reliably rotating the ball-valve
from closed to fully open. A Speedaireâ
ninety degree actuator with a 2-inch bore performs well.
Propellant heater. A system for heating the pressurized propellant
mix after transfer to the pressure vessel must be provided. This
would include a hot-air gun directed toward the pressure vessel,
a hot wire wrap, or other suitable means.
Pressure Gauge. A suitable device for measuring the pressure
of the contents must be installed on the simulator pressure vessel.
The device must be capable of measuring the pressure to within
+ 5 psi.
Propellant Mix. The base product/propellant mix should consist
of 20% liquid propane (C3H8 , 3.2 ounces),
60 % ethanol (denatured alcohol, 9.6 ounces), and 20% water (3.2
ounces) The total weight of the base product/propellant mix should
be 16 ounces.
Spark Igniters. A set of direct current (D.C) spark igniters
must be used to ignite the propellant/base product mix as it
is discharged from the pressure vessel. An ignition transformer
capable of providing 10,000 Volts output has been found to be
suitable for powering the igniters, which should be placed 36
inches (91.4 cm) from the point of discharge. The spark igniter
gap should be set at 0.8 inches (2 cm).
The procedure for conducting the aerosol simulator test is
as follows:
The procedure for conducting the aerosol simulator test is
as follows:
Weight the empty simulator device on a suitable scale. Place
the 9.6 ounces of ethanol (denatured alcohol) and 3.2 ounces
of water into the pressure vessel. Transfer 3.2 ounces of liquid
propane from a storage tank into the pressure vessel. Remove
all transfer lines and check final mass. Mount simulator device
in either the forward or aft compartment bulkhead such that discharge
is directed into the compartment, across spark igniters. Simulator
discharge port and the spark igniter must be 2 feet above the
compartment floor. Begin heating the pressure vessel to raise
the pressure of the contents to 240 +/- 5 psi. Activate the suppression
agent/system. Activate the spark igniters. Release the charged
contents into the compartment when the concentration of agent
is within +/-0.1% of the minimum design concentration.
4.4 SUPPRESSION SYSTEM DESIGN.
The suppression system design used for these fire tests should
be similar to the design intended for use in aircraft. For a
gaseous total flood system, the quantity of agent used should
be that quantity that will produce the same initial concentration
by volume in an empty 2000 cubic foot compartment as the design
concentration that will be demonstrated in the required flight
test in the actual aircraft cargo compartment. Some aircraft
total flood system designs consist of single bottle discharges,
multiple bottle discharges at staggered intervals, and single
bottle discharges followed by metered systems that bleed smaller
quantities of agent into the compartment to maintain the desired
concentration. The compartment volume, leakage rate, and diversion
time for the aircraft determines the type of system necessary.
There may be situations when the volume, leakage rate and 30
minute test duration required by these fire tests would not allow
for the use of the same system design as is intended for installation
in an aircraft. One possible situation could be when the leakage
from the actual aircraft cargo compartment is much lower than
what is required for the fire test and a single bottle discharge
is sufficient to maintain adequate concentration in the aircraft
but not in the fire test article. For this and other situations
that require changing the system design, a metered system may
be used to maintain adequate concentration of agent. The concentration
that should be maintained for the fire test should be the minimum
design concentration that the system will demonstrate can be
maintained by the required flight test. If a metered system is
used in the fire test, the concentration in the compartment after
the metered system is started should not be allowed to go higher
than 10% above the minimum design concentration. The concentration
should be measured at heights of 16", 32.5" and 49".
The readings from these three heights should be averaged to determine
the cargo compartment agent concentration.
For a non-gaseous suppression system, parameters such as activation
set points, operating pressures, nozzle spacing and direction,
etc. should be the same as the system intended to be installed
in the actual aircraft. Other factors that are cargo compartment
size dependent such as agent quantity, number of nozzles, zone
sizes, etc. should be scaled up or down as appropriate when the
volume and/or shape of the compartment in the actual aircraft
is different than the 2000 cubic foot compartment required for
these tests.
4.5 SUPPRESSION SYSTEM ACTIVATION.
Bulk load, Containerized load and Surface Burning fire scenarios:
The suppression system should be activated 60 seconds after any
one of the ceiling mounted thermocouples exceeds 200 degrees
F.
Aerosol can scenario: For a gaseous total flood suppression
system, the aerosol can simulator should be activated when the
agent concentration 2 feet above the compartment floor is at
the minimum volumetric design concentration +/- 0.1%. The agent
concentration must be actually measured during this test. Calculation
of agent concentration based on the leakage rate is not permitted.
The sampling probe for measuring agent concentration should be
36 inches from the exit of the aerosol simulator, at the location
of the spark igniters. For a suppression system that is not a
total flood gaseous system, the aerosol simulator should be positioned
at the most difficult location for that particular system.
4.6 TEST DURATION.
The duration of the bulk load and containerized load fire
scenario tests shall be for 30 minutes after the activation of
the suppression system. The surface burning fire test shall be
conducted for five minutes from the time the suppression system
is activated or until the fire is extinguished, whichever occurs
first. There is no time duration required for the exploding aerosol
test scenario.
5. ACCEPTANCE CRITERIA
The acceptance criteria for the surface burning fire scenario
is that none of the ceiling or sidewall temperatures exceed 500
degrees F. starting 30 seconds after the suppression system is
initially activated until the end of the test.
The criteria for the bulk load fire scenarios is that none
of the ceiling or sidewall thermocouples exceed 730 degrees F.
starting 30 seconds after the suppression system is initially
activated until the end of the test. In addition the area under
the time-temperature curve for the ceiling thermocouple that
recorded the highest temperature cannot exceed 11600 degrees
F.- minutes. The area should be computed from the time of initial
suppression system activation until the end of the 30 minute
test duration. The criteria for the containerized load fire scenario
is that none of the ceiling or sidewall thermocouples exceed
670 degrees F. starting 30 seconds after the suppression system
is initially activated. The area under the time-temperature curve
for the ceiling thermocouple cannot exceed 15700 degrees F.-
minutes. The area should be computed from the time of initial
suppression system activation until the end of the 30 minute
test duration. These values for the bulk and containerized fires
are based on an approximately 10% increase over the maximum values
obtained in a series of tests conducted under the requirements
of this MPS using Halon 1301 as the suppression agent.
The criteria for the aerosol can scenario is that none of
the ceiling and sidewall temperatures exceed 500 degrees F. at
any time and that the pressure rise in the compartment does not
exceed the pressure rise resulting from the same test using Halon
1301 at a concentration of 3%. Five tests must be conducted for
each scenario. The suppression system must successfully meet
the acceptance criteria for 5 of 5 tests.